Categories

LP350X Hose

INDUSTRIAL HOSE

RECOMMENDED FOR Liquid or gaseous propane, butane or any combination of these two mixtures up to 350 psi rated working pressure. Can be used for natural gas under certain conditions such as: open/outside areas and well ventilated factory buildings (if local building codes permit). Not recommended for residential or office buildings. Contact Denver

Product Application (303) 744–5070 for inspection and assembly testing information. Meets UL Standard #21, CAN/CGA–8.1–M86, NFPA 58, Section 8–3, 5.

TUBE Nitrile. See Hose Stock Characteristics.

REINFORCEMENT Braided, high–tensile synthetic textile cord.

COVER Black perforated Polychloroprene. See Hose Stock Characteristics.

TEMPERATURE RANGE –40°F to +180°F (–40°C to +82°C). For water emulsions see Temperature Limits Table.

COUPLING RECOMMENDATION GLX® Couplings (G44) Section N Power Crimp® Couplings (–12) Section I (See Crimp Data Manual 428–7365 or eCrimp)

Application Note: No LP350 hose assemblies 60″ or longer allowed per UL requirement